Knürr CoolDesk® |
|
| |
|
|
| |

• Possibility of connecting to
existing piping in the raised floor.
• Connection to building system
with the option of integrating
the Knürr CoolTrans® for
constantly even water supply.
• Solution via chiller, connection to
a complete Knürr supply system.
• Only one water flow required!
No airflow routing. This saves
space, cost and energy.
• Separate heat exchanger in
superstructure and underdesk
installation space. |
|
| |
|
|
| |
 |
|
| |
|
|
| |
Active monitor and room cooling
Technical Data:
•
Cooling performance: unit for room and monitor cooling : 1,1kW
•
Cooling performance: unit for room and monitor cooling : 1,7kW (0,85kW each side)
•
Max. noice level at the workingstation: 38 dB (A)
•
Temperature of the air in the underdesk construction: 20°C
•
Pressure stage of the water supply: PN10
•
Maintenance-free heat exchanger
•
2 fans for air inlet
•
Chilled water supply G 3/4“ male thread
•
Chilled water return G 3/4 male thread
•
Waterpipes are routed in the lowest level of the installation space, under the computers
•
No condensation
•
Floor plate of warkstation can be designed as tray
•
Magnetic valve for leaking detection in the underdesk construction
Carrying capacity:
•
1500 N (static load)
Hint:
•
The air circulation is a patented system.
•
The cooled air is routed in a horizontal air-flow system to the rear side of the PC-computers. |
|
| |
|
|
| |
Single Workstation
Technical Data:
•
Cooling performance: 3700 W
•
Max. noise power level at workstation: 38 dB (A)
•
Air-supply temperature in furniture: 20-25°C
•
Pressure level pipework: PN10 bar
•
2 fans to pull-in hot air (Maintenance-free)
•
Inside temperatur can be set with manual valve.
•
Control valve with screw joints (shut off, hydr. alignment, air bleeding, checking flow rate)
•
Chilled water supply G 3/4“ male thread
•
Chilled water return G 3/4“ male thread
Carrying capacity:
•
1500 N (static load)
Material/ surfaces
•
Three layer particel board, coated with high pressure plastic laminate
•
Worktops in fire protection class B 2
•
Underdesk installation space made of sheet-steel: RAL 7021 blackgrey
•
Superstructure: RAL 9006 aluminium |
|
| |
|
|
| |
Double Workstation
Technical Data:
•
Cooling performance: 2400 W
•
Max. noice level at the workingstation: 38 dB (A)
•
Temperature of the air in the underdesk construction: 20-25°C
•
Pressure stage of the water supply: PN10
•
Maintenance-free heat exchanger
•
2 fans for air inlet
•
Chilled water supply G 1 ¼“ male thread
•
Chilled water return G 1 ¼“ male thread
•
Waterpipes are routed in the lowest level of the installation space, under the computers
•
No condensation
•
Floor plate of warkstation can be designed as tray
•
Magnetic valve for leaking detection in the underdesk construction
•
Two redundant fans: If one fails, the second keeps the system alive
Carrying capacity:
•
1500 N (static load)
Material/ surfaces
•
Three layer particel board, coated with high pressure plastic laminate
•
Worktops in fire protection class B 2
•
Underdesk installation space made of sheet-steel: RAL 7021 blackgrey
•
Superstructure: RAL 9006 aluminium |
|
| |
|
|
| |
|
|